Rockwell Automation 1336T FORCE Series B User Manual
Page 61

Chapter 2
Installation/Wiring
2–41
Figure 2.28.
Option L6/L6E Wiring
Typical of Each Input
L6, L6E Options
A
A
ENC
RET
ENC
12V
115V AC
Fuse
Common
Typical
12V
681
100
90.9
5V
JP4
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
0.15
µ
f
0.33f
0.22
µ
f
49
499k
20k
100
100
User Supplied
115V AC
Contacts shown are general, refer to Figure 2.24 for
Input Mode selection and recommended contact types.
Fuse
TB3
NOT
USED
Option L6/L6E – 115V AC Interface Board Requirements
Circuits used with Option L6/L6E must be capable of operating with high
= true logic. In the low state, circuits must generate a voltage of no more
than 30V AC. Leakage current must be less than 10 mA into a 6.5k ohm
load. In the high state, circuits must generate a voltage of 90–115V AC
+/–10% and source a current of approximately 20 mA for each input.
The L6/L6E option is compatible with these Allen–Bradley PLC modules:
•
1771–OW
•
1771–OA
•
1771–OWN
•
1771–OAD (contact factory for recommended series/
rev. level.)