Chapter 5
Programming Parameters
5–62
Vqe Maximum (Constant HP)
[Vqe Max]
Parameter Number
244
Parameter Type
Sink
Display Units
x.x volts
Drive Units
16 = 1 volt (L–N)
Factory Default
367.0 volts
Minimum Value
0.0 volts
Maximum Value
468.8 volts
Vde Minimum (Constant HP)
[Vde Min]
Parameter Number
245
Parameter Type
Sink
Display Units
x.x Volts
Drive Units
16 = 1 volt line to neutral peak
Factory Default
3.0 volts
Minimum Value
0.0 volts
Maximum Value
50.0 volts
Kslip (Base Slip Frequency)
[Base Slip Freq]
Parameter Number
246
Parameter Type
Sink
Display Units
x.xx Hz
Drive Units
256 = 1Hz/unit torque
Factory Default
0.832 Hz
Minimum Value
0.000 Hz
Maximum Value
10.000 Hz
Q axis voltage at which the motor enters
field weakening. Parameter calculated by
autocommissioning routine and MUST
NOT BE CHANGED. Data represented as
x.x volts
D axis voltage below which the adaption to
motor changes in the torque control is dis-
abled. Parameter calculated by autocom-
missioning routine and MUST NOT BE
CHANGED. Data represented as x.x volts
Base slip frequency of the motor.
Parameter calculated by autocommission-
ing routine. Data represented as x.x Hz.
Kslip Maximum
[Base Slip Fr Max]
Parameter Number
247
Parameter Type
Sink
Display Units
x.xx Hz
Drive Units
256 = 1Hz/unit torque
Factory Default
2.00 Hz
Minimum Value
0.00 Hz
Maximum Value
30.00 Hz
Maximum slip frequency allowed on the
motor. Parameter calculated by autocom-
missioning routine and MUST NOT BE
CHANGED. Data represented as x.x Hz.
Kslip Minimum
[Base Slip Fr Min]
Parameter Number
248
Parameter Type
Sink
Display Units
x.xx Hz
Drive Units
256 = 1Hz / unit torque
Factory Default
0.50 Hz
Minimum Value
0.00 Hz
Maximum Value
10.00 Hz
Minimum slip frequency allowed on the
motor. Calculated by autocommissioning
routine and MUST NOT BE CHANGED.
Data represented as x.x Hz.
Ki – Slip Regulator
[Ki Slip]
Kp – Flux Regulator
[Kp Flux]
Kp – Slip Regulator
[Kp Slip]
Parameter Number
251
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
300
Minimum Value
0
Maximum Value
32767
Parameter Number
250
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
306
Minimum Value
0
Maximum Value
32767
Parameter Number
249
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
153
Minimum Value
0
Maximum Value
32767
Proportional Gain of the slip regulator.
This parameter MUST NOT BE
CHANGED.
Data represented as x.
Integral Gain of the slip regulator. This
parameter MUST NOT BE CHANGED.
Data represented as x.
Proportional Gain of the Flux regulator.
This parameter MUST NOT BE
CHANGED.
Data represented as x.