Rockwell Automation 1336T FORCE Series B User Manual
Page 49

Chapter 2
Installation/Wiring
2–29
Interface Board Installation and Removal –
IMPORTANT: If the L Option Board is being installed, Standard Adapter
Board jumpers at pins 3 & 4 and 17 & 18 of J10 must be removed and the
proper Input Mode selected (Figure 2.16). If the L Option board is
removed, these jumpers must be reinstalled and the Input Mode parameter
must be programmed to “1”.
Figure 2.16.
Interface Board Jumper Locations
JOG
ESC
SEL
Figure 2.17.
Reference Signal Connections (Standard Adapter Board)
TB5
1
2
3
4
5
6
7
8
9
10 11 12
TB6
13 14
TB7
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10 11 12
+10V
–10V
Com
+
–
SH
+
–
+
–
4 to 20ma
0 to
±
10V
SH
SH
+
–
Pulse
Source
0 to
±
10V
+
–
SH
+
–
0 to
±
10V
4 – 20 ma
SH
+
–
Analog
Outputs
Run
Fault
Relay
Alarm
Relay
TE
TE
Program
mable*
Run
Fault
Alarm
Terminal #
TB5
Signal
SH
Shield Ground
1,2,3
DC Power Supply
4,5,6,7
Input Impedance = 20K Ohms
10,11
Pulse Input for
Frequency Ref.:
+5V DC – Jumper xx Set to xx
+12V DC – Jumper xx Set to xx
Scale Factor (Pulse PPR) must be set
TB6
SH
1,2,4,5
Shield Ground
0 to +/– 10 V
DC Output:
Output Impedance = 100 Ohms
7,8
4 – 20 ma DC Output
Input Impedance = 130 Ohms
13,14
4 – 20ma Input:
Output Impedance = 100 Ohms
TB7
TE
4,5,6
Logic Earth Ground / Shield Ground
Fault Contact
Resistive Rating = 115VAC/30VDC, 5.0A
Inductive Rating = 115VAC/30VDC, 2.0A
7,8,9
Alarm Contact
Resistive Rating = 115VAC/30VDC, 5.0A
Inductive Rating = 115VAC/30VDC, 2.0A
Programmable
Supply
Note: This output is programmable through P384
If using a
potentiometer
reference* 2.5K
Ω
minimum
* External to Drive
DC Power Supply
+/– 10VDC, 50 mA per voltage
Output Impedance = 20 Ohms
User Supplied Analog Device
0 to +/– 10V DC Input:
Terminal Block