Rockwell Automation 1336T FORCE Series B User Manual
Page 181

Chapter 5
Programming Parameters
5–55
External Torque Step
[Ext Torque Step]
Parameter Number
166
Parameter Type
Sink
Display Units
x.x %
Drive Units
4096 @ rated motor torque
Factory Default
0.0%
Minimum Value
– 800.0%
Maximum Value
+ 800.0%
This parameter supplies an external torque
offset to the Drive. The Ext Torque Step is
summed with the Torque Mode Sel (P53)
output prior to the Torque Limiter.
Internal Torque Reference
[Int Torque Ref]
Parameter Number
167
Parameter Type
Source
Display Units
+/– x.x %
Drive Units
4096 = rated torque
Factory Default
+0.0 %
Minimum Value
–800.0%
Maximum Value
+800.0%
This parameter shows the value of torque
reference that is present at the output of
the torque limiter.
Internal Iq Reference
[Internal Iq Ref]
Parameter Number
168
Parameter Type
Source
Display Units
+/– x.x%
Drive Units
4096 = rated torque
Factory Default
+0.0 %
Minimum Value
– 800.0%
Maximum Value
+ 800.0%
This parameter shows the value of the Iq
reference that is present at the output of
the Iq rate limiter. 4096 is 100% Iq motor
current.
Torque Reference Testpoint Data
[Torque Ref TP]
Parameter Number
172
Parameter Type
Source
Display Units
+/– x.x%
Drive Units
4096 = 100% (1.0 pu)
Factory Default
+ 0.0%
Minimum Value
– 800.0%
Maximum Value
+ 800.0%
This parameter indicates the value of the
internal location selected by the Torq Ref
TP Sel parameter, P173. The select will
allow this parameter to be used as a test-
point for the torque
reference input.
Torque Reference Testpoint Select
[Torq Ref TP Sel]
Parameter Number
173
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
31
Enums:
This parameter selects which internal loca-
tion of the torque reference will become the
testpoint value. The value based on the
select will be stored in the Torque Ref TP
(P172).
Select Value
Torque Reference Access Point
Select Value
Torque Reference Access Point
0
Zero
17
Torque Reference Status
1
NTC Limit
18
Torque Reference Math Overflow Status
2
Inverter Current Limit
19
Active Torque Mode
3
Overload Current Limit
20
Positive Torque Power Limit
4
Positive IQ Limit
21
Negative Torque Power Limit
5
Negative Iq Limit
22
Rated Inverter Current
6
Zero (Not Used)
23
Averaged Motor Flux
7
Torque Limit (Low)
24
lq Current Reference Adjusted for Motor Range
8
Torque Limit (High)
25
lq Sum
9
Scaled External Torque Reference 1
26
Torque Mode Select lq Ref
10
Scaled External Torque Reference 2
27
Inverter Gain
11
Torque Sum
28
Motor Range
12
Torque Command
29
Motor to Inverter Current Ratio
13
Filtered Torque Reference
30
DC Bus Ride-Thru Latch
14
Unlimited Iq Reference
31
Current Processor Regulation Active Flag
15
Current Limited Iq Reference
16
Filtered Iq Reference