Chapter 5
Programming Parameters
5–40
Over Setpoint 3
[Over Setpoint 3]
Parameter Number
64
Parameter Type
Sink
Display Units
+/– x.x%
Drive Units
4096 = 100.0% setpoint
Factory Default
+0.0 %
Minimum Value
–800.0%
Maximum Value
+800.0%
Over Setpoint 4
[Over Setpoint 4]
Parameter Number
65
Parameter Type
Sink
Display Units
+/– x.x %
Drive Units
4096 = 100% setpoint
Factory Default
+0.0 %
Minimum Value
–800%
Maximum Value
+800%
This parameter is used to specify the set-
point threshold for the Over Setpoint 3 bit
in Logic Status Hi.
This parameter is used to specify the set-
point threshold for the Over Setpoint 4 bit
in Logic Status Hi.
Current Setpoint Tolerance
[Cur Setpoint Tol]
Parameter Number
68
Parameter Type
Sink
Display Units
x.x%
Drive Units
4096 = 100.0% Iq
Factory Default
2.0%
Minimum Value
0.0%
Maximum Value
20.0%
This parameter establishes a hysteresis
band around the Setpoints. It will be used
to determine when to update the Setpoint
Bits in Logic Status Hi (P57), when config-
ured for commanded current option.
Speed Setpoint Tolerance
[Speed Setpnt Tol]
Parameter Number
67
Parameter Type
Sink
Display Units
x.x rpm
Drive Units
4096 = base speed
Factory Default
base sp / 100
Minimum Value
0.0 rpm
Maximum Value
base speed /10
This parameter establishes a hysteresis
band around the At Setpoints. It will be
used to determine when to update the Set-
point Bits in the Logic Status Hi (P57),
when configured for actual speed option.
Zero Speed Tolerance
[Zero Speed Tol]
Parameter Number
69
Parameter Type
Sink
Display Units
+/– x%
Drive Units
4096 = base speed
Factory Default
base speed / 100
Minimum Value
0.0 rpm
Maximum Value
8 x base speed
This parameter establishes a band around
zero speed that will be used to determine
when to update the At Zero Speed bit in
the Logic Status Low (P56).
Setpoint Select
[Setpoint Select]
Parameter Number
66
Parameter Type
Sink
Display Units
Bits
Drive Units
bit clear = speed, set = current
Factory Default
0000 0000 0000 0000
Minimum Value
0000 0000 0000 0000
Maximum Value
0000 0000 1111 1111
Enums:
This parameter makes a selection between
actual speed or internal Iq current refer-
ence for the At/Over Setpoint parameters.
Each Setpoint Status bit can be set for ei-
ther option ( 0 = Actual Speed; 1 = Iq Ref-
erence).
Bit 0 = At Setpoint 1
Bit 1 = At Setpoint 2
Bit 2 = Over Setpoint 1
Bit 3 = Over Setpoint 2
Bit 4 = Over Setpoint 3
Bit 5 = Over Setpoint 4
Logic Testpoint Data
[Logic Tstpt Data]
This parameter contains the logic control
testpoint data that has been selected by
the Logic Tstpt Sel parameter, P71.
Parameter Number
70
Parameter Type
Source
Display Units
Bits
Drive Units
None
Factory Default
0000 0000 0000 0000
Minimum Value
0000 0000 0000 0000
Maximum Value
1111 1111 1111 1111