For each condition that you want the drive to display a warning fault on,
you need to:
1. Set the corresponding bit in CP Warning / None Configuration Select
2. Make sure the corresponding bit in CP Fault / Warning Configuration
Select is set to 0.
When the drive trips on a condition that you set to display a warning:
•
The CP light flashes green.
•
The drive continues to run.
If a particular bit is not set in either CP Fault / Warning Configuration
Select or CP Warning / None Configuration Select, the drive ignores the
condition when it occurs.
Most of the fault/warning configuration options deal with DC bus
conditions. These bus conditions deal with the bus precharge and any
type of ridethrough conditions. The bus precharge and ridethrough
conditions are covered later in this chapter.
bit = 1
bit = 0
Trips Drive
Fault
Fault Select
Reports as Warning
bit = 1
bit = 0
Reports as Warning
Warning Select
No Report, Ignored