Rockwell Automation 1336T FORCE Series B User Manual

Page 205

Advertising
background image

Chapter 5
Programming Parameters

5–79

SCANport Analog2 Select
[SB Analog2 Sel]

Parameter Number

367

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

1

Minimum Value

1

Maximum Value

6

Enums:

This parameter selects which SCANport
analog device is used in parameter 368
‘SB Analog In 2’.

1

Scanport 1

2

Scanport 2

3

Scanport 3

4

Scanport 4

5

Scanport 5

6

Scanport 6

SCANport Analog2 In
[SB Analog2 In]

Parameter Number

368

Parameter Type

Source

Display Units

+/– x

Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

This parameter displays the analog value
of the SCANport device selected in
parameter 367 ‘SP Analog2 Sel’.

SP Analog2 Scale
[SB Analog2 Scale]

Parameter Number

369

Parameter Type

Sink

Display Units

+/–x

Drive Units

+/– 1, 1 = 32767

Factory Default

1 (32767)

Minimum Value

–1 (–32767)

Maximum Value

1 (32767)

This parameter can be used to scale the
value in Parameter 368.

Analog Output 1
[Analog Out 1]

Parameter Number

370

Parameter Type

Sink

Display Units

+/–x

Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

This parameter converts a +/– 32767
digital value to a +/– 10 volt output.

Analog Output 1 Offset
[An Out 1 Offset]

Parameter Number

371

Parameter Type

Sink

Display Units

+/– x.xxx volt

Drive Units

205 = 1 volt

Factory Default

+0.000 volt

Minimum Value

–20.000 volt

Maximum Value

+20.000 volt

This parameter determines the offset
applied to the raw analog output 1. The
offset is applied after the scale factor.