Chapter 5
Programming Parameters
5–81
Milli Amp Output Scale
[mA Output Scale]
Parameter Number
378
Parameter Type
Sink
Display Units
+/– x.xxx
Drive Units
32767 = 1
Factory Default
+0.500
Minimum Value
–1.000
Maximum Value
1.000
This parameter determines the scale factor
or gain for milli amp output. A +/– 32767
digital value is converted by the scale fac-
tor which allows an effective digital range
of +/– 2048 which is then offset to provide
a +/– 20 mA range.
SCANport Analog Output
[SP Analog Out]
Parameter Number
379
Parameter Type
Sink
Display Units
+/–x
Drive Units
None
Factory Default
0
Minimum Value
–32767
Maximum Value
+32767
This parameter displays the analog value
that is sent to all SCANports
Programmable Output Select
[Output Select]
Parameter Number
384
Parameter Type
Sink,
Display Units
x
Drive Units
None
Factory Default
8
Minimum Value
0
Maximum Value
63
This parameter selects the function of
TB7–1 Output. The NOT column in the
following table indicates the value for the
inverse condition. For example: Entering
a value of 0 will result in a Run Ready
condition, while a value of 32
results in a NOT Run Ready condition.
NOT EN
32
0
RUN READY
33
1
RUNNING
34
2
COMMAND DIRECTION
35
3
ROTATING DIRECTION
36
4
ACCELERATING
37
5
DECELERATING
38
6
WARNING
39
7
FAULTED
40
8
AT SET SPEED
41
9
LOCAL A
42
10 LOCAL B
43
11 LOCAL C
44
12 AT ZERO SPEED
45
13 REF A
46
14 REF B
47
15 REF C
NOT EN
48
16 FLUX READY
49
17 FLUX UP
50
18 DIAGNOSTIC COMPLETED
51
19 DIAGNOSTIC ABORTED
52
20 BUS RIDETHRU
53
21 JOGGING
54
22 AUTOTUNE STAT A
55
23 AUTOTUNE STAT B
56
24 AT LIMIT
57
25 NOT USED
58
26 AT SETPOINT 1
59
27 AT SETPOINT 2
60
28 OVER SETPOINT 1
61
29 OVER SETPOINT 2
62
30 OVER SETPOINT 3
63
31 OVER SETPOINT 4
Set P66 to the type of Set Point desired,
Current or Speed.
Then set the appropriate parameter (P60 –
P65) to monitor your desired SetPoint.