Rockwell Automation 1756-HIST2G FactoryTalk Historian ME 2.2  User Manual

Page 100

Advertising
background image

F

ACTORY

T

ALK

H

ISTORIAN

ME M

ODULE

U

SER

S

G

UIDE

90

„

Treats conditions other than Any as Any.

The EVENT keyword:

„

Requires a trigger condition for it to function properly.

„

Allows a space, comma, or semicolon to separate trigger definitions.

I

NSTRUMENT

T

AG

The Instrument Tag field is used for the full path to the controller. If a source tag
receives events from a controller, the tag in this field will read (or write back) events
from the controller. The tag name syntax is:

<controller_name>.<tag_name>

Keyword

Trigger

Condition

Description

Example

TRIG

The condition is always Any.

EVENT

Any

EVENT

Nonzero

Trigger on any non-zero
value.

An event is triggered on a
value change from “Pt
Created” to 1 but it is not
triggered on a value
change from 1 to “bad
Input”.

EVENT

Anychange

Trigger on any change as
long as the value of the
current event is different
from the value of the
previous event.

An event will be triggered
on a value change from 0
to “bad Input” or from
“bad Input” to 0.

EVENT

Increment

Trigger on any increase in
value.

An event will be triggered
on a value change from 0
to 1.

EVENT

Decrement

Trigger on any decrease in
value.

An event will be triggered
on a value change from 1 to
0.

Advertising