Point Configuration

This section lists considerations related to point configuration.

Point Creation

„

You can create a maximum of 2500 data points per module. If you exceed 2500
data points, the Create button will automatically become deactivated. You can
deselect points from the Select field. The Create button will automatically become
reactivated when the point count is less than 2510 data points.

„

The maximum number of events per second for tags is 2500. For Data Collection
rates slower than 500ms, use Polled and Advised tags.

„

Avoid using High Speed points for Trigger Input and Output tags.

Add Points Wizard

If Data Collection is running during the Add Points Wizard process, you will be
prompted to stop and restart Data Collection after creating points for optimal
performance.

Point Properties

This section describes settings found on the Point Property page that you should
consider when configuring tags.

G

ENERAL

The General section of the Point Property page allows you to configure the following
parameters:

Scan Types

Scan Rate Recommendation

High Speed

Equal to or greater than 0.01 seconds
and
Equal to or less than 0.5 seconds

Advised
Polled

Equal or greater than 0.5 seconds

Trigger Input
Output

Avoid using

High Speed

points

Advertising