Snapshot data points
displayed on the
Current Data page
contain timestamps
that are not being
updated:

Check the status of Data Collection on the Home page.

Navigate to Time Source > Controller in the web interface.
Check for a message that indicates that data collection has
discarded data.

If Data Collection status is “Running”, check the Collection
Rate in the System Status section in the left navigation bar.

„

Ensure that the Collection
Rate is zero; this confirms
that Data Collection is not
collecting data.

„

Go to the Web Diagnostics
Firmware tab, and check
the Data Sever page. N/A
indicates an error state.

„

Reboot the module.

„

If Data Collection stops
again, go to the Configure
Historian
tab, and click
Data Storage. Ensure that
the Archive Disk Threshold
and Archive Usage Thresh-
old are still valid. If these
thresholds have been
reached, wait for the system
to process overflow events
and return to a state that
allows you to restart Data
Collection.

„

If the Collection Rate is not
zero, check the status of the
Data Server on the Home
page.

„

If the Point Server status is
“Stopped” or “Error”,
reboot the module.

If the Data Collection status is “Stopped”, go to the Data
Collection
page and restart Data Collection.

A single point has not
collected data for a
significant time
period:

„

Check the point configuration on the Point Property page.

„

Ensure that the scan rate is not set too low, and ensure that
the Exception and Compression values are configured
properly for the point.

Data Collection

Symptom

Solution