Auto recovery issues – Rockwell Automation 1756-HIST2G FactoryTalk Historian ME 2.2  User Manual

Page 307

Advertising
background image

G • T

ROUBLESHOOTING

297

Auto Recovery Issues

This section contains information that may help you troubleshoot FactoryTalk
Historian ME auto recovery.

Data Export

Symptom

Solution

The export function in
the Historian ME web
interface does not
work:

„

Verify that Microsoft Office Excel version 2007 or 2003
and lower is installed.

„

Open the Registry Editor, navigate to the
HKEY_CLASSES_ROOT > .csv folder, and verify that
the PerceivedType key is present and has a value of text
or document.

For any issue, follow the guidelines provided in the “General Guidelines” section of this
appendix.

Auto Recovery

Symptom

Solution

The time on the
module has moved to a
past time. This causes
existing archives to
have future
timestamps or
overlapping archives:

„

First, check the module’s time source to ensure that it is
correct. See information in “Time Management Issues” to
resolve time source issues.

„

If the issue is not a time source issue, restore the module to
its proper state by rebooting it. The module will start in
safe mode.

„

Click Safe Mode that initially displays when the module is
rebooted. (Safe Mode indicates that your system is in safe
mode.)

„

Download archives to retain the archive data for your
records.

„

Next, delete the archives with future timestamps or over-
lapping archives. See “Repairing Archives” for more
information.

Advertising