The System Status
section on the Home
page shows that Data
Collection is in
“Error” mode:

„

Check the module STS LED light. Solid red indicates that
Data Collection is inactive.

„

Go to the Advanced tab to view the System Log page.
Check the log for messages about the issue and export log
data.

„

Go to the Web Diagnostics Firmware tab, and check the
Data Collection page. Process information can confirm
whether or not Data Collection is in an undesirable state.

N/A indicates an error state.

„

Download additional information that will assist in trouble-
shooting as described in “General Guidelines”.

„

Reboot the module.

„

Contact Technical Support if the issues persists.

Tags are collecting bad
quality data:

FactoryTalk Historian ME’s support of controllers with
version 18 firmware assumes that the user makes no online
changes to a tag’s external access attribute. If your controller
is running version 18 firmware and you change a tag’s
external access attribute to “none”, then the data collected by
that tag for FactoryTalk Historian ME will be bad quality. To
fix this issue, you must change the tag value to either “Read/
Write” or “Read only” and reboot the module. This will solve
the problem.

Data Collection

Symptom

Solution