It is critical that you controller’s time is set, configured, and synchronized
properly. If your FactoryTalk Historian ME application uses the high speed scan
type (collecting data between 10ms and 500ms), the controller generates the
timestamp.

„

NTP Server

Select the NTP Server radio button, and enter the IP address or host name of the
NTP server. NTP servers are typically maintained by a corporate IT department
and are often the Windows Active Directory server on the network.

„

Historian SE/PI Server (which must be configured as an NTP server)

Select the Historian SE/PI Server radio button to synchronize the FactoryTalk
Historian ME time with a FactoryTalk Historian SE or PI server’s time. Before
selecting this option, you must:

‡

Configure a FactoryTalk Historian SE or PI server as a valid NTP server.
Contact your local system administrator to ensure that this NTP server is
configured and maintained properly.

and

‡

Specify the FactoryTalk Historian SE or PI server in Data Transfer.

When shutting down a FactoryTalk Historian SE or PI server that has been
configured as an NTP server, the server may take some time to shut down. Before
restarting the FactoryTalk Historian SE or PI server, make sure that the w32time
service is running on the FactoryTalk Historian SE or PI server machine. This
service must be running for the time to synchronize properly. If the w32time
service is not running, start the service, and then start the FactoryTalk Historian
SE or PI server.

„

Manual Set

Select the Manual Set radio button to manually set the time of FactoryTalk
Historian ME. The time is kept by the module’s real-time clock.

The RSLogix 5000 installation CD contains a Logix5000 Clock Update tool. The tool
lets you view and synchronize the system time of the controllers and devices on a
network, using any PC running Microsoft Windows and RSLinx Classic. For more
information about using this tool, see the Logix5000 Clock Update tool online help.

See the “Connecting to a FactoryTalk Historian SE or PI Server” section in the
“Transferring Data” chapter.