Use the table below to estimate performance impact. Note that Compression and
Exception Filtering data storage information in this table is an estimate. Actual
compressed data storage ranges will vary with the volatility of the data collected.

To calculate the total events per second, tags divided by the scan rate have to be
summed up per scan class for the module:

Sample Application

Estimate

1GB Module

2GB Module

2500 events per second without

Compression or Exception Filtering

4 hours

14 hours

2500 events per second with

Compression

and Exception Filtering

1 day

3 days

500 events per second with

Compression

and Exception Filtering

5 days

2 weeks

100 events per second with

Compression

and Exception Filtering

1 month

3 months

2500 events per minute without

Compression or Exception Filtering

10 days

1 month

2500 events per minute with

Compression

and Exception Filtering

2 months

6 months

500 events per minute with

Compression

and Exception Filtering

10 months

2.5 years

100 events per minute with

Compression

and Exception Filtering

4 years

10+ years