Compression Min

Value that indicates events are archived if the elapsed time since
the previous event is greater than or equal to the minimum time,
and the event value has changed by more than the deviation.
The value is expressed as dd hh mm ss.
Typically, the Compression Min should be 0.

Compression Max

Value that indicates events are archived if the elapsed time is
greater than the maximum time.
The value is expressed as dd hh mm ss.
The recommended maximum time specification is one work shift
(such as, eight hours). Duplicate values will be archived if the
elapsed time exceeds the Compression Max. Under no
circumstances does this cause the FactoryTalk Historian ME
server to generate events; it only filters events that are externally
generated.

Compression
Deviation

Value for the most important compression specification.
Setting this value too low causes too little data compression and
wastes space in the archive. Setting this value too high causes
loss of useful data. For most flows, pressures, and levels, use a
deviation specification of 1% or 2% span. For temperatures, the
deviation should usually be one or two degrees.