Input data tags – Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual

Page 116

Advertising
background image

116

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

Appendix B

Tag Definitions

Input Data Tags

Table 16

lists the input data tags.

C.Out[0].LowLimit

REAL

Defines the minimum value the output can use in the process. If an output beneath the low limit is requested, the
C.Out[0].LLimit alarm is set and the output signal will remain at the configured low limit.

C.Out[0].HighLimit

REAL

Defines the maximum value the output can use in the process. If an output above the high limit is requested, the
C.Out[0].HLimit alarm is set and the output signal will remain at the configured high limit.

C.Out[1]

AB:1756_IF4FXOF2F
_Struct_Out:C:0

Master structure beneath which configuration parameters for output channel 1 are set. This is the same set of tags as listed for
input channel 0, from

C.Out[0].HoldForInit

to

C.Out[0].HighLimit

, except that this listing applies to channel 1.

Table 15 - Configuration Data Tags (continued)

Tag Name

Data Type

Definition

Table 16 - Input Data Tags

Tag Name

Data Type

Definition

I.ChannelFaults

INT

Collection of individual channel fault bits in one word. Can address individual channel fault via bit notation, such as
ChannelFaults.3 for channel 3. Output channels are bits .4 and .5.

I.In0Fault

BOOL

Individual channel fault status bit that indicates a hard fault has occurred on the channel. One of the following conditions sets
this bit:
Calibration is ongoing.
An overrange condition is present.
An underrange condition is present.
Communication is lost with the I/O module.

I.In1Fault

BOOL

Individual channel fault status bit that indicates a hard fault has occurred on the channel. One of the following conditions sets
this bit:
Calibration is ongoing.
An overrange condition is present.
An underrange condition is present.
Communication is lost with the I/O module.

I.In2Fault

BOOL

Individual channel fault status bit that indicates a hard fault has occurred on the channel. One of the following conditions sets
this bit:
Calibration is ongoing.
An overrange condition is present.
An underrange condition is present.
Communication is lost with the I/O module.

I.In3Fault

BOOL

Individual channel fault status bit that indicates a hard fault has occurred on the channel. One of the following conditions sets
this bit:
Calibration is ongoing.
An overrange condition is present.
An underrange condition is present.
Communication is lost with the I/O module.

I.Out0Fault

BOOL

Individual channel fault status bit that indicates a hard fault has occurred on the channel. One of the following conditions sets
this bit:
Calibration is ongoing.
A low clamp condition is occurring.
A high clamp condition is occurring.
Communication is lost with the I/O module.

I.Out1Fault

BOOL

Individual channel fault status bit that indicates a hard fault has occurred on the channel. One of the following conditions sets
this bit:
Calibration is ongoing.
A low clamp condition is occurring.
A high clamp condition is occurring.
Communication is lost with the I/O module.

I.ModuleFaults

INT

Collection of all module level fault bits.

Advertising