Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

75

Configure the Module

Chapter 5

Communication Format

The communication format determines the following:

Available configuration options

Type of data transferred between the module and its owner-controller

Tags that are generated when the configuration is complete

Connection between the controller writing configuration and the module
itself

Table 12

lists the possible communication format choices. In addition to the

description below, each format returns status data and rolling timestamp data.

Electronic Keying

When you write configuration for a module you can choose how specific the
keying must be when a module is inserted into a slot in the chassis. The following
electronic keying options are available:

Compatible Module

Disable Keying

Exact Match

For more information on electronic keying, see

page 25

.

Use the Default
Configuration

If you use the default configuration and click Finish, you are done.

Table 12 - Communication Formats on the High-speed Analog I/O Module

Format

Definition

Archiving Connection

Module stores 20 input data samples for each channel in the module’s on-board
buffers before it sends the I/O data to the controller.

Float Data

Module returns floating point data.

CST Timestamped Float Data

Module returns floating point data with the value of the system clock (from its local
chassis) when the data is sampled.

Listen-only CST Timestamped
Float Data

Module returns floating point data with the value of the system clock from its local
chassis when the data is sampled to a controller that does not own the module.

Listen-only Float Data

Module returns floating point data to a controller that does not own the module.

IMPORTANT

Once the module is created, the communication format cannot be changed.
The module must be deleted and recreated.