Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual
Page 78
![background image](/manuals/579503/78/background.png)
78
Rockwell Automation Publication 1756-UM005B-EN-P - January 2013
Chapter 5
Configure the Module
Click here to accept the
parameters you have configured
for your module
Click Next to proceed.
Click Finish to accept the
parameters you have configured
for your module.
Click Next to proceed.
Choose an output channel.
IMPORTANT: Set all the parameters
for each channel before proceeding.
Set the Program mode output state.
If you click User Defined Value, you
must type a value in the box. You can
also choose to ramp to the value.
Set the output state in
Fault mode.
Choose an output channel.
IMPORTANT: Set all the parameters
for each channel before proceeding.
Set the clamp limits (
).
Pay attention to the clamp limits when
changing a channel from current to
voltage. The software does not
automatically account for the mode
change. You must also take into
account how changes may affect your
engineering units.
If necessary, check the Ramp in Run
Mode checkbox (
).
If you check the Ramp in Run Mode
checkbox, you must type a ramp rate
(
).
Disable all alarms.
Latch limit alarms
(
).
Set the output state if communication
fails in Program mode.