Install the Module
Chapter 4
Connect the Grounded End of the Cable
1.
Ground the drain wire.
2.
Connect the insulated wires to the field-side.
Connect Ungrounded End of the Cable
1.
Cut the foil shield and drain wire back to the cable casing and apply shrink
wrap.
2.
Connect the insulated wires to the RTB, as shown below.
IMPORTANT
We recommend you ground the drain wire at the field-side. If you
cannot ground at the field-side, ground at an earth ground on the
chassis as shown below.
20104-M
a. Remove a length of cable
jacket from the Belden cable.
b. Pull the foil shield and bare drain
wire from the insulated wire.
c. Twist the foil shield and drain
wiretogether to form a single
strand.
d. Attach a ground lug and apply
heat shrink tubing to the exit
area.
20918-M
e. Connect the drain wire to a chassis
mounting tab. Use any chassis
mounting tab that is designated as a
functional signal ground.
4M or 5M (#10 or #12)
Star Washer
4M or 5M (#10 or #12)
Phillips Screw and Star
Washer (for SEM screw)
Chassis Mounting Tab
Drain Wire with Ground Lug