Connect the wiring – Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual
Page 60

60
Rockwell Automation Publication 1756-UM005B-EN-P - January 2013
Chapter 4
Install the Module
Connect the Wiring
You can use an RTB or a Bulletin 1492 prewired Interface Module (IFM) to
connect wiring to your module. An IFM has been prewired before you received
it. If you are using an IFM to connect wiring to the module, skip this section and
move to
.
If you are using an RTB, connect wiring as directed below. We recommend you
use Belden 8761 cable to wire the RTB. The RTB terminations can
accommodate 22…14 AWG shielded wire.
Before wiring the RTB, you must connect ground wiring.
WARNING: If you connect or disconnect wiring while the field-side power is on,
an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.
ATTENTION: When using the 1756-TBCH RTB, do not wire more than two
0.33...1.3 mm
2
(22...16 AWG) conductors on any single terminal. Use only the
same size wires with no intermixing of solid and stranded wire types.
When using the 1756-TBS6H RTB, do not wire more than one conductor on any
single terminal.