Chapter 6

Calibrate the Module

3.

Verify the operating range for each channel. You must use the correct
operating range for each channel being calibrated or calibration will not
work. For example, if you want to calibrate channel 0 in Voltage mode, it
must be set for the -10…10V range.

4.

Go to the Output Calibration page to begin calibration.

This example shows the calibration range for each channel.

5.

Select the output channels that you want to calibrate.

Choose the channel.

Make sure each channel is using the correct

operating range. If the operating range is

incorrect, use the pull-down menu to change

the range. You must apply any changes to the

module before proceeding.

Click here to begin
calibration.

Select the outputs here.

This example shows Channel 0 using

Voltage mode and Channel 1 using Current

mode. Because the channels use different

modes, the software requires that you

calibrate them separately and disregards

the Calibrate Channels in Groups setting.

Click Next to proceed.