Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual
Page 92

92
Rockwell Automation Publication 1756-UM005B-EN-P - January 2013
Chapter 6
Calibrate the Module
3.
Verify the operating range for each channel. You must use the correct
operating range for each channel being calibrated or calibration will not
work. For example, if you want to calibrate channel 0 in Voltage mode, it
must be set for the -10…10V range.
4.
Go to the Output Calibration page to begin calibration.
This example shows the calibration range for each channel.
5.
Select the output channels that you want to calibrate.
Choose the channel.
Make sure each channel is using the correct
operating range. If the operating range is
incorrect, use the pull-down menu to change
the range. You must apply any changes to the
module before proceeding.
Click here to begin
calibration.
Select the outputs here.
This example shows Channel 0 using
Voltage mode and Channel 1 using Current
mode. Because the channels use different
modes, the software requires that you
calibrate them separately and disregards
the Calibrate Channels in Groups setting.
Click Next to proceed.