Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual

Page 31

Advertising
background image

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

31

Module Features

Chapter 3

EXAMPLE

In this scenario, Disable Keying allows I/O communication.

The module configuration is for a 1756-IA16 digital input module. The physical
module is a 1756-IB16 digital input module. In this case, communication is
allowed because the two digital modules share common data formats.

IMPORTANT

Changing electronic keying selections online may cause the I/O
communication connection to the module to be disrupted and may result in a
loss of data.

Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IA16
Major Revision = 2
Minor Revision = 1

Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16
Major Revision = 3
Minor Revision = 2

Communication is allowed.

Advertising