Chapter

7

Troubleshoot the Module

Use Module Indicators
to Troubleshoot

The module uses the status indicators shown below.

Status indicators on the module provide the current status of the module, as
described in

Table 13

.

Topic

Page

Use Module Indicators to Troubleshoot

97

Use the Logix Designer Application to Troubleshoot

98

Table 13 - Status Indicators for Input Modules

Indicator

Status

Description

OK

Steady green

The inputs are being multicast and in normal operating state.
The outputs are in Run mode.

OK

Flashing green

The module has passed internal diagnostics but is not currently performing
connected communication or is in Program mode. Inputs are in a normal
operating state. Outputs are in the configured state for Program mode.

OK

Flashing red

Previously established communication has timed out.
Check controller and chassis communication.

OK

Steady red

The module must be replaced.
Replace the module.

CAL

Flashing green

The module is in Calibration mode.

ANALOG OUTPUT

CAL

OK

42878

ANALOG INPUT