7 - troubleshoot the module, Use module indicators to troubleshoot, Chapter 7 – Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual
Page 97: Troubleshoot the module, Chapter

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013
97
Chapter
7
Troubleshoot the Module
Use Module Indicators
to Troubleshoot
The module uses the status indicators shown below.
Status indicators on the module provide the current status of the module, as
described in
Table 13
.
Topic
Page
Use Module Indicators to Troubleshoot
Use the Logix Designer Application to Troubleshoot
Table 13 - Status Indicators for Input Modules
Indicator
Status
Description
OK
Steady green
The inputs are being multicast and in normal operating state.
The outputs are in Run mode.
OK
Flashing green
The module has passed internal diagnostics but is not currently performing
connected communication or is in Program mode. Inputs are in a normal
operating state. Outputs are in the configured state for Program mode.
OK
Flashing red
Previously established communication has timed out.
Check controller and chassis communication.
OK
Steady red
The module must be replaced.
Replace the module.
CAL
Flashing green
The module is in Calibration mode.
ANALOG OUTPUT
CAL
OK
42878
ANALOG INPUT