Input channel status word bits – Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual

Page 52

Advertising
background image

52

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

Chapter 3

Module Features

Input Channel Status Word Bits

Table 10

defines the Input Channel Status word bits.

Table 10 - Input Channel Status Word Bit Description

Bit

Name

Description

Bit 8

I.In[x].ChanFault

This bit matches the state of I.InxFault bits (0-3) in the Channel Fault word, except
when a communication fault occurs. If a communication fault occurs between the
module and its owner-controller, the I.InxFault bit is set but this bit is not set.
Bit is set if one of the following events occurs:
The module is being calibrated.
An underrange condition exists on input channel.
An overrange condition exists on input channel.

Bit 7

I.In[x].CalFault

Bit is set if an error occurs, and is not corrected, during calibration for that channel.

Bit 6

I.In[x].Underrange

Bit is set when the input signal at the channel is less than or equal to the
minimum detectable signal.

Bit 5

I.In[x].Overrange

Bit is set when the input signal at the channel is greater than or equal to the
maximum detectable signal.

Bit 4

I.In[x].RateAlarm

Bit is set when the input channel’s rate of change exceeds the configured Rate
Alarm parameter. It remains set until the rate of change drops below the
configured rate. If latched, the alarm will remain set until it is unlatched.

Bit 3

I.In[x].LAlarm

Bit is set when the input signal moves beneath the configured Low Alarm limit. It
remains set until the signal moves above the limit. If latched, the alarm remains
set until it is unlatched. If a deadband is specified, the alarm also remains set as
long as the signal remains within the configured deadband.

Bit 2

I.In[x].HAlarm

Bit is set when the input signal moves above the configured High Alarm limit. It
remains set until the signal moves below the limit. If latched, the alarm remains
set until it is unlatched. If a deadband is specified, the alarm also remains set as
long as the signal remains within the configured deadband.

Bit 1

I.In[x].LLAlarm

Bit is set when the input signal moves beneath the configured Low-Low Alarm
limit. It remains set until the signal moves above the limit. If latched, the alarm
remains set until it is unlatched. If a deadband is specified, the alarm also remains
latched as long as the signal remains within the configured deadband.

Bit 0

I.In[x].HHAlarm

Bit is set when the input signal moves above the configured High-High Alarm
limit. It remains set until the signal moves below the limit. If latched, the alarm
remains set until it is unlatched. If a deadband is specified, the alarm also remains
latched as long as the signal remains within the configured deadband.

Advertising