Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

95

Calibrate the Module

Chapter 6

If the measurement is within an acceptable range, the channel is marked
with an OK status, such as shown below. If the measurement is not within
an acceptable range, the software returns you to

step 8

until the module

produces an acceptable output low reference level.

10.

Repeat

step 6

through

step 9

to calibrate output channel 1 for 0…20 mA

operation.

When you have successfully calibrated both channels, the following
parameters appear.

This completes calibration of input and output channels.

Click Next to continue.

Click Finish to complete the calibration.