Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

Chapter 6

Calibrate the Module

If the measurement is within an acceptable range, the channel is marked
with an OK status, such as shown below. If the measurement is not within
an acceptable range, the software returns you to

step 6

until the module

produces an acceptable output low reference level.

8.

Command the output channel to produce a high voltage reference level.

9.

Record the results shown on your voltage calibrator.

Click Next to proceed.

0.0021

The software commands the
output channel 0 to produce a high
voltage reference of 10.00V.

Click Next to proceed.

Record the voltage
measurement.

Click Next to proceed.