Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual

Page 91

Advertising
background image

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

91

Calibrate the Module

Chapter 6

To calibrate the high-speed analog module’s outputs, follow these steps.

1.

Connect your current or voltage meter (depending on what mode your
channel is operating in) to the module. Remember, that you must wire the
module differently for Current mode than for Voltage mode. To see how to
wire for each mode, see

page 63

.

2.

Access the module’s properties page.

The Module Properties dialog box appears.

Choose Properties.

Right-click I/O Configuration

to see the menu.

Click the Output Configuration tab.