Rockwell Automation Publication 1756-UM005B-EN-P - January 2013
91
Calibrate the Module
Chapter 6
To calibrate the high-speed analog module’s outputs, follow these steps.
1.
Connect your current or voltage meter (depending on what mode your
channel is operating in) to the module. Remember, that you must wire the
module differently for Current mode than for Voltage mode. To see how to
wire for each mode, see
2.
Access the module’s properties page.
The Module Properties dialog box appears.
Choose Properties.
Right-click I/O Configuration
to see the menu.
Click the Output Configuration tab.