Fault reporting example, Module fault word bits, Fault reporting example module fault word bits – Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual

Page 50

Advertising
background image

50

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

Chapter 3

Module Features

Fault Reporting Example

Figure 10

shows an example of what bits are set when a ControlLogix high-speed

analog I/O module reports a Wire Off condition on output channel 0. Three
events occur, beginning in the Output Channel Status word.

Figure 10 - Fault Reporting for Wire Off Condition

The following sections provide a listing and explanation of the bits included in
each of the module’s fault reporting words.

Module Fault Word Bits

Table 8

defines the Module Fault word bits.

15

14

13 12

11

5

4

3

2

1

0

5

4

3

2

1

0

7

6

When set, the I.Out0Fault bit (bit 4) sets the I.OutGroupFault bit (bit 13) and the
I.AnalogGroupFault bit (bit 15).

43175

8

When set, I.Out[0].WireOff bit sets the I.Out0Fault bit (bit 4) in the
Channel Fault word.

When the Wire Off condition on channel 0 occurs, the I.Out[0].WireOff bit (bit 5) in the
Output Channel Status word is set.

5

4

3

2

1

0

7

6

8

Table 8 - Module Fault Word Bit Descriptions

Bit

Name

Description

Bit 15

I.AnalogGroupFault

Bit is set when any of the bits in the Channel Fault word are set.

Bit 14

I.InGroupFault

Bit is set when any of the input channel fault bits in the Channel Fault word are
set.

Bit 13

I.OutGroupFault

Bit is set when any of the output channel fault bits in the Channel Fault word are
set.

Bit 12

I.Calibrating

Bit is set when any of the module’s channels are being calibrated. When this bit is
set, all used bits in the Channel Fault word are set.

Bit 11

I.CalFault

Bit is set when an individual channel calibration fault bit, such as I.In[0].CalFault,
is set.