Process alarms – Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual

Page 44

Advertising
background image

44

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

Chapter 3

Module Features

Process Alarms

Process alarms (configured in engineering units) alert you when the module has
exceeded configured high or low limits for each input channel. You can latch
process alarms. These are set at four user configurable alarm trigger points:

High high

High

Low

Low low

You can configure an alarm deadband to work with these alarms. The deadband
lets the process alarm status bit to remain set, despite the alarm condition
disappearing, as long as the input data remains within the deadband of the
process alarm.

Figure 8

shows input data that sets each of the four alarms at some point during

module operation. In this example, Latching is disabled; therefore, each alarms
turns OFF when the condition that caused it to set ceases to exist.

Figure 8 - Process Alarms

To see how to set process alarms, see

page 77

. To see how to set the alarm

deadband, see

page 77

.

43153

High High

Low Low

Low

High

Alarm Deadbands

High high alarm turns OFF.
High alarm remains ON.

High high alarm turns ON.
High alarm remains ON.

Normal input range

Low low alarms turns OFF.
Low alarm remains ON.

High alarm turns OFF.

Low low alarms turns ON.
Low alarm remains ON.

Low alarms turns OFF.

Low alarms turns ON.

High alarm
turns ON.

Advertising