Output Data Tags

Table 17

lists the output data tags.

I.Out[0].ChanFault

BOOL

Copy of .Out0Fault in array with other channel status bits for ease of access.

I.Out[0].CalFault

BOOL

Status bit indicating if the channel has a bad calibration. Bad calibration means the last attempt to calibrate the channel failed
with an error and was aborted.

I.Out[0].WireOff

BOOL

Bit that indicates a wire has fallen off the output channel. This bit is functional only when C.Out[0].Range is set to operate in
0…20 mA mode.

I.Out[0].NotANumber

BOOL

Bit indicating the received output value from the controller (value in O.Data[0] tag) was an invalid IEEE floating point value.
When an invalid value is received, the output value holds its last known valid state.

I.Out[0].InHold

BOOL

Bit that indicates if the output channel is currently holding until the Output value sent to the module (value in O.Data[0] tag)
matches the current output value (value in O.Data[0] tag) within 0.1% of the channel’s full scale.

I.Out[0].RampAlarm

BOOL

Alarm bit that sets when the requested output value (C.Out[0].RampToRun) is set, and the difference between the new output
value requested and the current output exceeds the configured ramp limit (C.Out[0].MaxRampRate). The bit remains set until
ramping ceases unless the alarm is latched via C.Out[0].RampAlarmLatch.

I.Out[0].LLimitAlarm

BOOL

Alarm bit that sets when the requested output value (O.Data[0]) is below the configured low limit (C.Out[0].LowLimit). In this
case, the output stops at the configured low limit; the stop is reflected in the data echo. This bit remains set until the requested
output moves above the low limit unless latched by C.Out[0].LimitAlarmLatch.

I.Out[0].HLimitAlarm

BOOL

Alarm bit that sets when the requested output value (O.Data[0]) is above the configured high limit (C.Out[0].HighLimit). In this
case, the output stops at the configured high limit. The stop is reflected in the data echo. This bit remains set until the
requested output moves below the high limit unless latched by C.Out[0].LimitAlarmLatch.

I.Out[0].Data

REAL

Value the channel outputs (in engineering units) based on the configured scaling for the channel.

I.Out[1]

AB:1756_IF4FXOF2F
_Struct_Out:I:0

Array for output channel 1. This is the same set of tags as listed for input channel 0, from

I.Out[0].Status

to

I.Out[0].Data

,

except that this listing applies to channel 1.

I.CSTTimestamp

Array of DINT

Timestamp taken when input data is sampled. This value is listed as a 64-bit quantity in microseconds and coordinated across
the chassis. Must be addressed in 32-bit chunks as an array.

I.RollingTimestamp

INT

Timestamp taken when input data is sampled. This value is listed in milliseconds, relative solely to the individual module.

Table 16 - Input Data Tags (continued)

Tag Name

Data Type

Definition

Table 17 - Output Data Tags

Tag Name

Data Type

Definition

O.Out[0].Data

REAL[2]

The channel output value in engineering units. The output value is measured and scaled, based on the configured scaling for
the channel.

O.Data[0]

REAL

Output Channel 0.

O.Data[1]

REAL

Output Channel 1.

Advertising