Module resolution – Rockwell Automation 1756-IF4FXOF2F ControlLogix High-speed Analog I/O Module User Manual

Page 35

Advertising
background image

Rockwell Automation Publication 1756-UM005B-EN-P - January 2013

35

Module Features

Chapter 3

Understand Module
Resolution, Scaling
and Data Format

The following three concepts are closely related and must be explained in
conjunction with each other:

Module Resolution

Scaling

Module Resolution

Resolution is the smallest amount of change that the module can detect.
High-speed analog I/O modules are capable of 14-bit resolution. The 14 bits
represent 16,384 counts. Depending on the operating range, the available counts
varies, as shown in

Figure 4

.

Figure 4 - Available Counts

IMPORTANT

A module’s resolution is fixed. It does not change regardless of how you decide
to scale your module.

4096 Counts

-10V

0V

5V

10V

8192 Counts

16,384 Counts

0 mA

21 mA

8192 Counts

Voltage Resolution

Current Resolution

0…5V (actual limit = 5.25V)
Inputs Only

0…10V (actual limit = 10.5V)
Inputs Only

-10…10V (actual limit = -10.5V …10.5V)
Inputs and Outputs

0…21 mA
Outputs use 8192 counts of
current resolution.

4096 Counts

0 mA

21 mA

0 to 21 mA
Inputs use 4096 counts of
current resolution.

Advertising