Performance and Theory of Operations

Chapter 7

7-6

Setup #3

NOCV = 1 (VME coprocessor does not constantly read PLC processor)
Copy to global VME RAM off-board the PLC processor at 0x70000
Programming terminal attached to PLC processor monitoring ladder file

Command

Minimum msec.

Maximum msec.

Average msec.

CTV #N7:0 70000 D16 1

4.0

16.0

6.0

CTV #N7:0 70000 D16 500

7.0

18.0

10.0

CTV #N7:0 70000 D16 1000

11.0

21.0

13.0

CFV 70000 D16 #N7:0 1

5.0

15.0

7.0

CFV 70000 D16 #N7:0 500

8.0

19.0

11.0

CFV 70000 D16 #N7:0 1000

11.0

23.0

13.0

SVE 1 55

3.0

14.0

5.0

Setup #4

NOCV = 0 (VME coprocessor constantly read PLC processor)
Copy to global VME RAM on-board the PLC processor at 0xA00000
Programming terminal not attached to PLC processor

Command

Minimum msec.

Maximum msec.

Average msec.

CTV #N7:0 A0000 D16 1

6.0

11.0

7.0

CTV #N7:0 A0000 D16 500

10.0

14.0

12.0

CTV #N7:0 A0000 D16 1000

14.0

18.0

16.0

CFV A0000 D16 #N7:0 1

6.0

10.0

7.0

CFV A0000 D16 #N7:0 500

10.0

14.0

13.0

CFV A0000 D16 #N7:0 1000

14.0

19.0

18.0

SVE 1 55

4.0

8.0

6.0