Chapter 6

PLC-5/VME Processor
Communications Commands

6-9

See the “Header Bit/Byte Descriptions” section on page 6-4 for
descriptions of all bytes except the following:

Use the:

To specify:

PLC-5/VME processor
ADDR field

the address of the element(s) to be modified. You can use the 242-byte
address/mask field to modify selected words in and between data files.

AND mask (2-bytes
field)

which bits are reset to 0 in the addressed word. A 0 in the AND mask
resets the corresponding bit in the addressed word to 0. A 1 in the AND
mask leaves the corresponds bit unchanged. Low byte comes first in the
AND mask.

OR mask
(2-byte field)

which bits to set to 1 in the addressed word. A 1 in the OR mask sets to 1
the corresponding bit the addressed word. A 0 in the OR mask leaves the
corresponding bit unchanged. Low byte comes first in the OR mask.

Message Format

PLC-V5

DST

00

PSN

00

SRC

00

PSN

00

CMD

0F

STS

00

TNS

FNC

26H

Command Packet

LNH

Hi

LNH

Lo

DST

00

PSN

00

SRC

00

PSN

00

CMD

4FH

STS

Reply Packet

TNS

repeats, up to 242 bytes

AND

Lo

Hi

OR

Lo

Hi

EXT

STS

06

FF

FILE #

Lo

FF

ELEM #

Lo

PLC-V5 ADDR

Hi

Hi

ADDRESS

Error Codes

Extended status codes are reported in the response packet. The STS byte
contains 00H if no error, F0H when the PLC-5/VME processor detects an
error. If an error, the error code is indicated in the EXT STS byte
as follows:

STS

EXT STS

Description

00H

No error

F0H

01H

Illegal address—address field has an illegal value

02H

Illegal address—not enough fields specified

03H

Illegal address—specified too many address levels

06H

Illegal address—file does not exist

07H

Beyond end of file

0BH

Access denied—privilege violation

Refer to page D-3 for additional information on PCCC status codes.