Chapter 2

Installation

2-7

A remote I/O link using this communication rate:

Cannot exceed this cable length:

57.6 kbps

3,048 m (10,000 ft)

115.2 kbps

1,524 m (5,000 ft)

230.4 kbps

762 m (2,500 ft)

Prepare the Cable

Cut the cable according to the lengths you need. Route the cable to
the devices.

Make Remote I/O Connections

Use Figure 2.2 when connecting the remote I/O cable to PLC-5 processors
and remote I/O adapter modules.