Chapter 4

Ladder-Program Interfaces

4-13

Table 4.C
Fields for the Physical Structure of the VME Status File

Word

Code

Function

Explanation

6

2

FEN

From-VME enabled

If 1, the continuous-copy-from-VME operation is enabled (active when in run mode).

6

2

FAM

From-VME
address modifier

If 0, the continuous-copy-from-VME operation uses the 2D VMEbus address modifier (A16); if 1, it
uses 3D (A24).

6

2

FDS

From-VME data size

If 0, the continuous-copy-from-VME operation does D16 VMEbus transfers; if 1, it does D08(EO)
transfers.

6

2

FERROR

From-VME error code

If nonzero, refer to page 11 for the most-recent error.

8

2

FADDRESS (HI BYTE) Meaningful only if TAM=1

Address bits 23-16 of the address of the first byte of the VMEbus source.

9

2

FADDRESS

VMEbus source

Address bits 15-0 of the address of the first byte of the VMEbus source.

10

2

FLENGTH

From-VME copy length

The number of 16-bit words to be transferred by the continuous-copy-from-VME operation.

11

2

FFILE

From-VME file number

The number of the processor destination file of the continuous-copy-from-VME operation.

12

2

FELEMENT

From-VME
element number

The number of the first element to be transferred in the destination file of the continuous-copy-
from-VME operation.

13

2

FINT

From-VME interrupt

If nonzero, the VMEbus interrupt level of the interrupt to be generated after completion of each
continuous-copy-from-VME operation.
000 specifies no interrupt,
001 specifies interrupt level 1,
010 specifies level 2,
...,
111 specifies level 7.

14

2

FSTATUSID

From-VME status/ID

The VMEbus status/ID value transmitted during interrupt-acknowledge cycles of the
above interrupt.

15

2

TEN

To-VME enabled

If 1, the continuous-copy-to-VME operation is enabled (active when in run mode).

15

2

TAM

To-VME address modifier

If 0, the continuous-copy-to-VME operation uses the 2D VMEbus address modifier (A16);
if 1, it uses 3D (A24).

2

Both PLC ladder logic and the VME host computer can write to the status file fields that control the continuous-copy-from function. When both the ladder program and the host computer try to update the

status file simultaneously, the ladder program overwrites the changes made by the host.