Performance and Theory of Operations

Chapter 7

7-9

Effects of False versus True Logic on Scan Ti

me

The rung below—which changes states from one program scan to the
next—will change your scan time by about 400

ms.

NATURAL LOG
Source

Dest

N7:0

F8:20

I:000

00

LN

5

1.609438

If I:000/00 is:

Then the rung is:

On

true and the processor calculates the natural log. A natural-log instruction takes
409

µ

s to execute

Off

false and the processor scans the rung but does not execute it. It takes only 1.4

µ

s just to scan the rung.

Other instructions may have a greater or lesser effect.

Effects of Different Instructions on Logic Scan Time

Some instructions have a much greater effect on logic scan time than
others based on the time it takes to execute each instruction.

Program scan time is also affected by the basic construction of your ladder
rungs. The sizes of rungs and the number of branches in each can cause
the scan time to fluctuate greatly.

Effects of Different Input States on Logic Scan Time

You can write your logic so that it executes different rungs at different
times, based on input conditions. The different amounts of logic executed
in the logic scans causes differences in program scan times. For example,
the simple differences in rung execution in the following example cause
the logic scan times to vary.

00

JMP

Rung 1

B3:0

20

I:000

02

MVM

MVM

JMP

O:013

20

LBL

02

Rung 2

Rund 3

Rung 4