C - specifications, Environmental specifications, Specifications – Rockwell Automation 1785-Vx0B, D17856.5.9 PLC-5 VME VMEbus Programmable Controllers User Manual User Manual
Page 247

C
Appendix
C-1
Specifications
Characteristic
Value
Temperature
Operating
0-65
°
C at point of entry of forced air with 200 LFM of air flow
across the circuit board. Derated 2
°
C per 1000 ft (300m) over
6600 ft (2000m). 2
°
C per min max excursion gradient
Storage
-40
°
-85
°
C
5 C per min max excursion gradient
Humidity
Operating
0-90% noncondensing
Storage
0-95% noncondensing
Altitude
Operating
0-10,000 ft (3000 m)
Storage
0-40,000 ft (12,000 m)
Processor Weight
21 ounces (595 grams) PLC-5/V30
24 ounces (680 grams (PLC-5/V40, -5/V40L, -5/V80)
Vibration
Operating
0.015 inch (0.38 mm) P-P displacement with 2.5 g peak (max)
acceleration over 5-2000 Hz
Storage
0.030 inch (0.76 mm) P-P displacement with 5.0 g peak (max)
acceleration over 5-2000 Hz
Shock
Operating
30 g, 11 ms duration, half-sine shock pulse
Storage
50 g, 11 ms duration, half-sine shock pulse
Power
Maximum
21 watts
Typical
16 watts
Current
+ 5V
4.0 A (max), 3.2 A (typical)
Agency Certification (when
product or packaging is
marked)
CE marked for all applicable directives
Environmental
Specifications