Identify host and status, Message format – Rockwell Automation 1785-Vx0B, D17856.5.9 PLC-5 VME VMEbus Programmable Controllers User Manual User Manual

Page 75

Advertising
background image

Chapter 6

PLC-5/VME Processor
Communications Commands

6-6

Use this command to:

diagnostic command when debugging your host CPU’s driver program
confirm communication with the specified PLC-5/VME processor
identify its operating mode
report other useful information before initiating an upload or download

Message Format

DST

00

PSN

00

SRC

00

PSN

00

CMD

06

STS

00

TNS

FNC

03

Command Packet

LNH

Hi

LNH

Lo

DST

00

PSN

00

SRC

00

PSN

00

CMD

46H

STS

Reply Packet

TNS

STATUS (36 bytes)

See the “Header Bit/Byte Descriptions” section on page 6-4 for
descriptions of all bytes except the table on the next page.

The STATUS field returned in the reply packet indicates the following:

Byte

Description

1

Operating status of the PLC-5/VME processor

Bits 2-0

000 = program load

010 = run mode

100 = remote program load

101 = remote test

110 = remote run

001, 011, 111 = not used

Bit 3

0 = no fault

1 = major fault

Bit 4

0 = not downloading

1 = download mode

Bit 5

0 = not uploading

1 = upload mode

Bit 6

0 = not testing edits

1 = testing edits

Bit 7

0 = no edits in PLC-5/VME processor 1 = edits in processor

2

EBH

PLC-5/VME processor

3

38H

Processor expansion type

4-7

Processor Memory Size (96K bytes) (low word, low byte first)

8

Series and revision of PLC-5/VME processor

Bits 4-0

00000 = Revision A

00001 = Revision B, etc.

Bits 7-5

000 = Series A

001 = Series B, etc.

9

Processor station number

Bits 5-0

Station number 0-63

10

FDH

Future development

11

00H

Future development

Identify Host and Status