Handling the processor, Setting the switches – Rockwell Automation 1785-Vx0B, D17856.5.9 PLC-5 VME VMEbus Programmable Controllers User Manual User Manual

Page 24

Advertising
background image

Chapter 2

Installation

2-2

The processor is shipped in a static-shielded container to guard against
electrostatic damage. Electrostatic discharge can damage integrated
circuits or semiconductors in the processor module if you touch backplane
connector pins. It can also damage the module when you set configuration
plugs or switches inside the module. Avoid electrostatic damage by
observing the following precautions.

Remain in contact with an approved ground point while handling the

module (by wearing a properly grounded wrist strap).

Do not touch the backplane connector or connector pins.

When not in use, keep the module in its static-shielded container.

Before installing the PLC-5/VME processor, you need to make some
decisions about its configuration and operation and set the switches on the
circuit board accordingly. You need to know:

DH+ station (node) number

Memory protection—whether you want the processor’s program

RAM protected

Location of configuration registers in VMEbus A16 address space

System controller—whether you want the processor to serve as the

VMEbus slot-1 system controller

VMEbus request level—whether you want the processor to request

access to the VMEbus at level 3 or level 1

Figure 2.1
Switch Location

SW1

SW2

19502

Front plate

Bottom

Table 2.A and Table 2.B describe the switch settings for SW1.

Handling the Processor

Wrist strap

19897

DH+ station
number

Power-
up Test

Memory
protect

SW1 set of switches

Up
(off)

Down
(on)

1

2

3

4

5

6

7

8

Setting the Switches

Advertising