Chapter 6

PLC-5/VME Processor
Communications Commands

6-19

Important: The PLC-5/VME processor ADDR, OFFSET, and TOTAL
TRANS fields work together when the total number of words to be written
requires multiple packets.

Message Format

OFFSET

DST

00

PSN

00

SRC

00

PSN

00

CMD

0F

STS

00

TNS

FNC

67H

Command Packet

LNH

Hi

LNH

Lo

DST

00

PSN

00

SRC

00

PSN

00

CMD

4FH

STS

Reply Packet

TNS

up to 244 bytes

Lo

Hi

PLC-V5

a

EXT

STS

06

FF

FILE #

Lo

FF

ELEM #

Lo

PLC-V5 ADDR

Hi

Hi

ADDR

TOTAL

TRANS

a — data type ID code byte(s).
b — DATA byte field.

See Data Typed section

b

Error Codes

Extended status codes are reported in the reply packet. The STS byte
contains 00H if no error, F0H when the PLC-5/VME processor detects an
error. If an error, the error code is indicated in the EXT STS byte
as follows:

STS

EXT STS

Description

00H

No error

F0H

02H

Illegal address—not enough fields specified

03H

Illegal address—specified too many address levels

06H

Illegal address—file does not exist

07H

Illegal address—beyond the end of the file

0BH

Access denied—privilege violation

11H

Mismatched data type

Refer to page D-3 for additional information on PCCC status codes.