Chapter 2

Installation

2-13

82

W

resistor

Clear
Shield
Blue

Use the 3-pin connector on the processor to connect a DH+ link.
The connector’s port must be configured to support a DH+
communication link.

You can connect a DH+ link two ways:

trunkline/dropline—from the dropline to the connector screw
terminals on the DH+ connectors of the processor

daisychain—to the connector screw terminals on the DH+
connectors of the processor

To make connections:

1. Connect the signal conductor with CLEAR insulation to the

3-pin connector terminal 1 at each end of each cable segment.

2. Connect the SHIELD drain wire to the 3-pin connector SH

terminal at both ends of each cable segment.

3. Connect the signal conductor with BLUE insulation to the 3-pin

connector terminal 2 at each end of each cable segment.

For more information, see the Data Highway/Data Highway
Plus/Data Highway II/Data Highway 485 Cable Installation Manual,
publication 1770-6.2.2.

Chan 0

Chan 2

To connect a programming terminal via the 8-pin
connector on a PLC-5/VME processor on a DH+
link, use the following:

Communication card
to access a DH+ link

Cable

1784-PCMK

1784-PCM5 with a
1784-CP7 adapter

1784-KTX

1784-CP12 with a
1784-CP7 adapter
OR
1784-CP13 direct
connect to the front
of the PLC-5/VME
processor

8-pin
Mini-DIN

8-pin
Mini-DIN

PLC-5/V40B or -5/V80B

PLC-5/V40L

Programming Terminal

1784-CP6

1784-CP6