error codes are:

Code

Explanation

0000H

Success

0001H

Invalid ASCII message format

0002H

Invalid file type

0003H

invalid file number

0004H

Invalid file element

0005H

Invalid VME address

0006H

Invalid VME transfer width

0007H

Invalid number of elements requested for transfer

0008H

Invalid VME interrupt level

0009H

Invalid VME interrupt status-id value

000AH

VMEbus transfer error (bus error)

000BH

Unable to assert requested interrupt (already pending)

000CH

Raw data transfer setup error

000DH

Raw data transfer crash (PLC switched out of run mode)

000EH

Unknown message type (message type not ASCII)

Code

Explanation

01H

VMEbus transfer error (bus error)

07H

Bad data address

FDH

Bad data transfer length

FEH

Unacknowledged end-of-copy interrupt

These are the command-protocol codes placed in the error-code field of the
command control register when the ERR bit is 1.

Code

Explanation

00H

No error

01H

Invalid value in command register

02H

Cannot access first word of command block (usually a VMEbus bus error)

03H

Cannot access other than first word of command block

04H

Cannot write response word in command block

Message Completion and