Chapter 1

Overview

1-10

Table 1.B
Comparison of 6008-LTV and PLC-5/VME Processor Attributes

Attributes

6008-LTV

PLC-5/VME

Comments

VME slots

3

2

Bus arbitration

No

Yes or No (user configurable)

Single level arbiter

VME master

Yes

Yes

VME Slave

Yes

Yes

Global memory (bytes)

1

1K short, 4K short or standard

64K standard

Global memory is selectable

Programming and downloading
over backplane

No

Yes

With 6200 series software
release 4.4 and later

Saving over backplane

No

Yes

With 6200 series software
release 4.5 and later

PLC

data table to global memory trans-

fer method

Continuous-copy command

Continuous-copy and/or ladder
MSG commands

Asserts VME SYSFAIL

Yes

Yes

PLC resets upon VME SYSRESET

Yes

Yes

Bus request line

0, 1, 2, 3

1, 3

Bus release

ROR, RWD, ROC

ROR, RWD, ROC

Continuous-copy command file size

500 words

1000 words

Ladder MSG file size

N/A

1000 words

RS-232 port

No

Yes

Remote I/O baud rate

57.6k baud fixed

57.6k, 115.2k, 230.4k baud configurable

Remote I/O fractional rack addressing

No

Yes

1

All of the 6008-LTV’s global memory could be configured to be totally within short memory. Because the PLC-5/VME processor’s global memory would totally fill all of

VME short memory, it can only be selected with a standard memory address. This may be a consideration when replacing a 6008-LTV with a PLC-5/VME processor.

There are some areas of potential incompatibility to consider:

The configuration/control/status/message registers are slightly different,

requiring changes to the host driver program.

The LTV VME global memory can be selected to be in short or standard

memory space. The PLC-5/VME processor’s global memory can only
be selected to be in standard memory. Because of this, the 6008-LTV
will accept address modifiers 2D, 3D 29 and 39. The PLC-5/VME
processor will only respond to address modifiers 3D.

The 6008-LTV supports logical rack address 0; the PLC-5/VME

processor does not.

The 6008-LTV has a status/configuration bit to enable or ignore ROC

(release on clear). The PLC-5/VME processor will always respond
to ROC.