Once you connect the programming device through a local DH+ link to
one processor, the device can communicate with any PLC-5/VME
processor on the link. You can also communicate with PLC-2, PLC-3, and
PLC-5/250 processors connected to the link provided you have the
appropriate programming software installed.

The processor has electrically parallel DH+ connectors.

This processor:

Has these electrically parallel DH+ connectors:

PLC-5/V40B
PLC-5/V80B

8-pin connector for each of channel 1A and 2A

3-pin connector on each of channel 1A and 2A

Channels 1A and 2A must be configured to support DH+ communication
to use the connectors described above. Note that Channel 1A’s default
configuration is DH+ communication.

Channels 1B and 2B can also support DH+ communication if properly
configured, but they do not have parallel connectors.

PLC-5/V40L

8-pin connector for channel 1A

3-pin connector for channel 1A

Channel 1A must be configured to support DH+ communication to use the
connectors described above. Note that Channel 1A’s default configuration
is DH+ communication.

Channel 1B can also support DH+ communication if properly configured,
but it does not have parallel connectors.

Use the Belden 9463 twinaxial cable (1770-CD) to connect the processor
to the DH+ link.

Follow these guidelines while installing DH+ communication links:

do not exceed these cable lengths:

- trunkline-cable length—3,048 m (10,000 cable-ft)
- drop-cable length—30.4 m (100 cable-ft)

do not connect more than 64 stations on a single DH+ link