Performance and Theory of Operations

Chapter 7

7-14

Figure 7.3
PLC-5/V40L Timing Loops for Discrete Data Transfer

Adapter

Adapter

Adapter

Housekeeping

Rack 3

Rack 2

Rack 1

Remote I/O
Buffer

Logic
Scan

Remote I/O Scan
Timing Loop

Program Scan
Timing Loop

IOT (x)
IIN (y)

Immediate I/O

I/O Image

Table

Data

Exchange

Update
I/O Image

Data Exchange

a

b

a
write outputs

b
read inputs

x
y

Extended
Local
I/O Rack

Immediate I/O

The processor responds to immediate input (IIN) and immediate output
(IOT) requests during the logic scan. The logic scan is suspended at the
request for immediate input/output data. The logic scan resumes after
obtaining the data and fulfilling the request.

IIN and IOT data transfers directly to and from I/O modules in extended-
local I/O chassis. With remote I/O, only the remote I/O buffer is updated.

Transferring Block Data

The exchange of block-transfer data and the logic scan run independently
and concurrently. The following sections explain block-transfer for
extended-local I/O and then for remote I/O.

Extended-Local I/O

Requests for block-transfer data occur during the logic scan. Concurrent
with the execution of the logic, block-transfer requests are forwarded to the
appropriate 1771-ALX adapter module(s) and data is transferred. A
1771-ALX adapter module may start block-transfer operations to multiple
slots and have block-transfer data transactions on-going in parallel within
the 1771 chassis.