Configuration registers – Rockwell Automation 1785-Vx0B, D17856.5.9 PLC-5 VME VMEbus Programmable Controllers User Manual User Manual

Page 42

Advertising
background image

Chapter 3

VMEbus Interface

3-4

The configuration registers are a standard way of identifying, configuring,
controlling, and monitoring the PLC-5/VME processor as a VMEbus
device. They are mapped into the VMEbus A16 address space at a
location defined by switches 1-3 of SW2. For example, if these three
switches are set to ON, the first register (the ID register) is at address
FC00 (hex).

The registers are shown in Figure 3.1 and described individually thereafter.

Figure 3.1
The Eight Configuration Registers

ID Register

1

1

0

0

1

1

1

1

1

1

1

0

1

1

0

0

01

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

offset

Device-Type Register

0

1

1

1

1

1

1

1

1

1

1

0

1

0

0

0

03

Status/Control Register

GRE

1

1

SYSF

1

NOCV

1

1

SRIE

RELM MYAS

1

RDY

PASS NOSF RSTP

05

Offset Register

1

1

1

1

1

1

1

1

07

Command Control Register

WRDY LOCK

ERR

1

COPY-TO-STATE COPY-FR-STATE

ERROR CODE

09

Command Control and Lock Register

0B

Command High Register

0D

Command Low Register

0F

SLAVE BASE

WRDY LOCK

ERR

1

COPY-TO-STATE COPY-FR-STATE

ERROR CODE

C

F

E

C

7

F

E

8

00

offset

02

04

06

08

0A

0C

0E

Important: The system repeats these registers eight times; you can use
only the first eight registers as the configuration register.

These registers are described in detail below. Where a bit position has
been described as a 0 or 1, the bit is a read-only bit and writing to it has
no effect.

Configuration Registers

Advertising