Chapter 6

PLC-5/VME Processor
Communications Commands

6-5

Use this command to debug or test PCCC transmission capability. The
command packet can contain up to 243 bytes of data. The processor
simply returns (“echos”) the same data in the reply packet.

Message Format

DATA

DST

00

PSN

00

SRC

00

PSN

00

CMD

06

STS

00

TNS

FNC

00

Command Packet

LNH

Hi

LNH

Lo

DST

00

PSN

00

SRC

00

PSN

00

CMD

46H

STS

Reply Packet

TNS

up to 243 bytes

SAME DATA

up to 243 bytes

Error Codes

Extended status codes are reported in the response packet. The STS byte
contains 00H if no error, F0H when the PLC-5/VME processor detects an
error. If an error, the error code is indicated in the EXT STS byte
as follows:

STS

EXT STS

Description

00H

No error

F0H

10H

Illegal command or format

20H

Host has a problem and will not communicate

30H

Remote station host is missing, disconnected, or shut down

40H

Host could not complete function due to hardware fault

50H

Addressing problem or memory protect rungs

60H

Function disallowed due to command protection selection

80H

Compatibility mode file missing or communication zone problem

90H

Remote station cannot buffer command

B0H

Remote station problem due to download

Refer to page D-3 for additional information on PCCC status codes.

Sample API Module

For a sample
interface
header file:

Refer to page:

For a sample
implementation
source file:

Refer to page:

P40VECHO.H

B-58

P40VECHO.C

B-59

Echo

Advertising