Appendix D

Troubleshooting

D-4

The codes returned in the EXT STS (extended status) field when the
remote error (STS) is F0H are listed below:

Code (hex)

Explanation

0

Not used

1

A field has an illegal value

2

Less levels specified in address than minimum for any address

3

More levels specified in address than system supports

4

Symbol not found

5

Symbol is of improper format

6

Address does not point to something usable

7

File is wrong size

8

Cannot complete request, situation has changed since start of command

9

Data or file is too large

A

Transaction size plus word address is too large

B

Access denied, improper privilege

C

Condition cannot be generated—resource is not available

D

Condition already exists—resource is already available

E

Command cannot be executed

F

Histogram overflow

10

No access

11

Illegal data type

12

Invalid parameter or invalid data

13

Address reference exists to deleted area

14

Command execution failure for unknown reason

15

Data conversion error

16

Scanner not able to communicate with 1771 rack adapter

17

Adapter cannot communicate with module

18

1771 module response was not valid

19

Duplicated label

1A

File is open; another node owns it

1B

Another node is the program owner

1C TO FF

Not used

If you receive a code other than the above, you are using a PCCC not
described in this manual and should consult the documentation you are
using to understand that PCCC and its specific error codes.