Chapter 2 – Rockwell Automation 1785-Vx0B, D17856.5.9 PLC-5 VME VMEbus Programmable Controllers User Manual User Manual

Page 31

Advertising
background image

Chapter 2

Installation

2-9

If your remote I/O link:

The maximum number of
racks you can scan on
the link

The maximum number of
physical devices you
can connect on the link

Use this resistor rating:

contains any device listed in Table 2.A

150

W

16

16

operates at 57.6 kbps or 115.2 kbps, and you do
not require the link to support more than 16
physical devices.

As shown in the table above, the terminators you use determine how many
devices you can connect on a single remote I/O link.

Table 2.A
I/O Link Devices that Require 150-

W

Termination Resistors

Device Type

Catalog Number

Series

Scanners

1771-SN
1 2 SD SD2

All

1772-SD, -SD2
1775-SR

1775-SR
1775-S4A, -S4B

1775 S4A, S4B
6008-SQH1, -SQH2

Adapters

1771-AS

1771-ASB

A

Miscellaneous

1771-AF

All

1771-DCM

Figure 2.3
Terminating a Remote I/O Link Using a Resistor

1

2

150

or
82

Blue

Shield

Clear

Blue

Shield

Clear

Blue

Shield

Clear

To

I/O adapter

19334

PLC-5/VME processor or remote I/O adapter module
as the last device on an remote I/O link.

Another I/O link device

Advertising